Preconstruction Site Evaluation Using Electrical Resistivity and Geotechnical Investigations in Al-Qasim District, Babylon Governorate, Iraq

Authors

  • Iman M. Jaafar Department of Geology, College of Science, University of Basrah, Basrah, Iraq https://orcid.org/0000-0002-1422-7615
  • Walaa M. Al-Mosawi Marine Science Center, University of Basrah, Basrah, Iraq
  • Yasmin I. Al Fraji Department of Geology, College of Science, University of Basrah, Basrah, Iraq
  • Amer A. Al-Khalidy Department of Applied Geology, College of Science, University of Babylon, Hella, Iraq https://orcid.org/0009-0000-2099-5306
  • Mohammed A. Haiwe Department of Geology, College of Science, University of Basrah, Basrah, Iraq

DOI:

https://doi.org/10.46717/igj.2026.59.1E.10

Keywords:

Electrical resistivity; SPT; Bearing capacity; Foundation design; Groundwater salinity; Babylon

Abstract

This work was conducted by performing resistivity and geotechnical investigations for a transformer electrical station proposed in Al-Qasim District, Babylon Governorate, to assess subsurface conditions and suitability for the station foundation. A total of five Vertical Electrical Soundings employing the Schlumberger array (AB/2=1.5–50 m) and two boreholes (10 m depth) with Standard Penetration Test were executed. The highly dissolved-sulfide groundwater table emerged at ∼a depth of 0.7 m. An indicative compaction and reduced saturation from the surface to a depth of 4 m were noted, with a positive correlation between electrical resistivity (15–90 Ωm) and Standard Penetration Test-N values (10–25). Resistivity decreased significantly below this depth due to the high salinity of the groundwater and the increase in clay content, while Standard Penetration Test-N increased (up to 30), indicating reduced reliability of the resistivity–Standard Penetration Test relationship under saline conditions. The cohesive soil exhibited low activity (PI= 30–41%) and over-consolidated behavior. The allowable bearing capacity ranged from 7.8–11.4 T/m² (dynamic method) to 6.73–9.42 T/m² (static method), and the soil consistency ranged from soft to medium stiff. To minimize compressibility and potential settlement issues, a compacted granular sub-base layer of 1.0–1.5 m thickness is recommended beneath shallow foundations, along with protective measures against sulfate attack.

Downloads

Published

2026-05-31